Have Questions, Need Further Details?
(+1)888 CEASEFIRE (232-7334)
CFCA 1 - 100LP
Cease Fire
The Cease Fire® CFCA 1 - 100LP is a self-activating unit. Each unit is designed to initiate automatically by means of a sprinkler head rated at 155ºF (68ºC). Alternative sprinkler head options are available, ranging from 135°F - 286°F. With custom applications reaching up to 1,800°F. The temperature rating for each sprinkler head is stamped on the star shaped deflector in both Fahrenheit and Celsius measurements. The temperature of the sprinkler head is fixed and must be designated at the time of purchase. When the temperature rise to activate the Cease Fire® unit, the sprinkler head opens automatically and dispenses the entire contents in less than 10 seconds onto the fire and throughout the enclosure being protected. If the unit is equipped with the optional pressure switch, a signal is sent at the time of discharge to activate accessory equipment, such as an alarm.
The LP in the naming of this CFCA denotes the orientation the unit is designed to be installed. LP standing for "Low Profile" and ment to be installed horizontal rather than vertical. When installed horizontally the unit takes up as little 3.5" of space. The naming of CFCA 1 - 100LP stands for the cubic volume that each unit can protect. Any space with a cubic volume of 1 - 100 feet can be protected by a single CFCA 1 - 100LP.
Suppressing Agent: FM-200 Clean Agent Gas
Maximum Total Flood Volume: 100 Cu. Ft. / 2.83 Cubic Meters
Design Concentration: 7% by Volume
Temperature Rating/Validation: 32°F to 120°F / 0°C to 49°C
Cylinder: Worthington/ Small DDI
Diameter: 3.5” / 8.90cm
Height: 10.5” + 3.5” Coupling Assembly / 26.67cm + 8.90cm
Capacity: 3.41 lbs / 1.55 kg
Unit Weight: 6.85 lbs / 3.11 kg
Ship Weight: 10.50 lbs / 4.76 kg
Operating Pressure: 175 psi / 1207 kPa
Propellant: High Purity Compressed Dry Nitrogen
Standard System Activation: 155° Fahrenheit / 68.3° Celsius
Designed and Tested by Cease Fire® in Accordance with NFPA-2001